Current Transformer Sizing Chart: Ratio and Accuracy Class

Author: Baoding Houfeng Trading Co., Ltd. — Power Monitoring and Testing Equipment Team
Reviewed by: Power Testing Engineering Team — senior engineers with 15+ years in substation and plant commissioning.
About us: Baoding Houfeng Trading Co., Ltd. supplies power monitoring and high-voltage test equipment to utilities and industrial plants worldwide.
Last updated: 2026-10-27

A current transformer sizing chart turns CT specification from a guess into a repeatable procedure: you read the load current, choose the ratio, pick the accuracy class, and confirm the burden fits — all from one table. The chart only works if you understand the few quantities that decide a current transformer, because the wrong ratio or an under-rated burden silently corrupts every measurement and protection decision made downstream of it. This guide walks a substation or plant engineer through those quantities step by step, with the chart itself and the rating tables you need to apply it.

What is current transformer

What is current transformer isolation, and why does it matter? The isolation is what lets a 110 kV feeder be measured by a 5 A panel instrument with no direct connection to the live conductor. A current transformer, or CT, is an instrument transformer that steps a primary current of hundreds or thousands of amperes down to a standard secondary of 1 A or 5 A so that a meter, relay or recorder can read it safely. It does this with a magnetic core and a secondary winding, where the primary is often just the busbar or cable passed once through the core window, and the secondary is wound many times around it. The turns ratio sets the nominal relationship, but the real output only matches the ideal ratio while the core stays away from saturation.

A cross-section of a current transformer showing the core, secondary winding, primary conductor and insulation
Figure 1 — The core, the secondary winding around it, the single-turn primary conductor and the insulation are the parts that decide how faithfully the secondary reproduces the primary.

The CT exists because protective relays and meters must never touch the high-voltage conductor directly. The secondary circuit is isolated from the primary by the core and insulation, which is what lets a 110 kV feeder be measured by a 5 A panel instrument. That isolation is also why the secondary must always be closed through a burden: opening it while the primary is energised collapses the demagnetising ampere-turns and drives the core into violent saturation, producing a dangerous overvoltage.

The CT comes in several physical forms, and the form partly decides how you size it. A window (toroidal) type clamps over a cable, a bar type has the primary built in, a wound type has a multi-turn primary winding, and a bushing type slides over a transformer bushing. A Rogowski coil is an air-cored alternative with no saturation, used where conventional cores would distort under high di/dt.

A comparison of five current transformer types across core, ratio and best-fit application
Figure 2 — Window, bar, wound, bushing and Rogowski designs each suit a different installation; the form constrains the ratio and the available accuracy class.

The current transformer sizing chart, step by step

Current transformer sizing starts with the load the CT must measure, not with a catalogue number. The primary rating is chosen from the maximum continuous load current, then given headroom so the unit is not pushed to its thermal edge every day: a common rule is to size the primary at 1.25 to 1.5 times the maximum load current (IEC 61869-2:2017 guidance on rating and burden), so a 400 A feeder normally lands near 400/1.5 ≈ 600 A and is specified as a 600/5 A or 600/1 A unit. Sizing from the load, not the cable, keeps the operating point inside the accurate band where the class is guaranteed.

The secondary current is then selected: 1 A is preferred for long cable runs and heavy fault currents because it keeps the lead resistance burden low, while 5 A remains common on short switchgear wiring. The choice matters for saturation maths later, because the same volt-drop across a smaller secondary current means a higher allowable lead resistance. After the ratio, the engineer picks the accuracy class for each duty the CT serves — metering, protection, or both on separate cores — and finally verifies the connected burden stays inside the rated VA.

A decision flow for choosing a CT accuracy class from the application
Figure 3 — The duty — metering or protection — decides the class family, and the fault level decides the accuracy limit factor or the IEEE C-rating.

The chart below is the working tool. Read down the application, take the ratio rule, the class and the burden, and you have a first-pass specification that still must clear the burden and saturation checks in the later sections.

ApplicationRatio ruleRecommended classRated burdenWhy
Revenue / sub-meteringLoad × 1.250.2S / 0.5S≤ 5 VAaccuracy held down to 1% of rated (IEC 61869-2:2017)
Feeder overcurrent protectionLoad × 1.55P20 / 10P2010–15 VAlinear to 20× rated
Transformer differentialfrom through-fault5P20 / PX15–30 VAknee-point voltage check needed
Motor protectionFLC × 1.55P10 / 5P205–15 VAtolerate locked-rotor inrush
HV bushing CT (IEEE)rated currentC400 / C800per relayterminal voltage at 20× rated
Audit—current transformer sizing chart—re-check whenever the load grows

This chart is only a starting point; the burden and saturation checks decide whether the chosen numbers survive a real fault. If the connected burden exceeds the rated VA, the core saturates earlier than the class promises, and the protection or metering accuracy collapses exactly when it matters most.

Current transformer rating chart

The rating chart is the companion to the sizing chart: it decodes the class marks on the nameplate into guaranteed errors and the current range where they hold. Metering classes (0.1, 0.2, 0.2S, 0.5, 0.5S, 1) are tight at normal load and deliberately saturate early under fault to protect the meter; the “S” variants hold their error down to 1% of rated (IEC 61869-2:2017) rather than the 5% floor of the non-S classes (IEC 61869-2:2017), which is why revenue metering uses 0.2S. Protection classes (5P, 10P, and PX for differential) stay linear into fault current, with the trailing number giving the accuracy limit factor.

ClassFamilyGuaranteed errorAccurate rangeTypical use
0.2SMetering±0.2% at rated (IEC 61869-2:2017)1–120% of ratedutility revenue billing
0.5SMetering±0.5% at rated (IEC 61869-2:2017)1–120% of ratedindustrial energy meters
5P20Protection±5% composite at 20× rated (IEC 61869-2:2017)up to 20× ratedfeeder overcurrent
10P20Protection±10% composite at 20× rated (IEC 61869-2:2017)up to 20× ratedmotor protection
C400Protection (IEEE)≤10% at 20× rated @ 400 V (IEEE C57.13-2016)up to 20× ratedtransformer bushings

In North American practice the IEEE C-class replaces the IEC P-system: a C400 CT can deliver its rated current into a burden that develops 400 V at 20 times rated primary current without exceeding 10% ratio error (IEEE C57.13-2016). The current transformer rating chart therefore has two dialects, and the engineer must read both when equipment spans IEC and IEEE markets. A 5P20 CT and a C400 CT are not interchangeable on paper even when they serve the same feeder, because one is specified by composite-error-at-ALF and the other by terminal voltage.

Standards you should match

The specification rests on four documents. IEC 61869-1:2023 is the general-requirements family standard for instrument transformers above 1 kV, covering ratings, markings and tests that every CT type inherits. IEC 61869-2:2017 adds the CT-specific limits: the metering and protection accuracy classes, the accuracy limit factor, the composite-error definition and the knee-point rule that a 10% rise in excitation voltage causes a 50% rise in excitation current (IEC 61869-2:2017). Those two are the bedrock of any credible CT data sheet.

A timeline of current transformer standards from IEC 60044 through IEC 61869-1:2023, IEC 61869-2 and IEEE C37.110-2023
Figure 4 — The IEC 60044 series was restructured into the IEC 61869 family, while IEEE C57.13 and the C37.110 application guide cover North American practice.

Across the Atlantic, IEEE C57.13-2016 sets the North American requirements and the C-class voltage ratings, while IEEE C37.110-2023 is the application guide for CTs used in protective relaying, including the saturation-screening criterion that compares fault current, burden and X/R against the knee-point or C-rating. Cite the measurement standard for the class and the application guide for the scheme, and keep the two separate in the report, exactly as the loading and rise limits were kept separate for temperature work.

References

  • IEC 61869-1:2023 — Instrument transformers, Part 1: General requirements. IEC Webstore
  • IEC 61869-2:2017 — Instrument transformers, Part 2: Additional requirements for current transformers. IEC Webstore
  • IEEE C57.13-2016 — IEEE Standard Requirements for Instrument Transformers. IEEE Standards
  • IEEE C37.110-2023 — IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes. IEEE Standards

Reading the nameplate and avoiding saturation

The nameplate is where sizing meets reality. A marking such as 600/5 A | 15 VA | 0.5 | 5P20 | IEC 61869-2 reads as ratio, rated burden, metering class, protection class and standard. The burden is the total VA of everything in the secondary loop — the meter or relay impedance, the lead resistance (proportional to cable length and inversely to cross-section) and the CT winding resistance — and it must stay at or below the rated VA or the core reaches saturation before the class promises.

Saturation is the failure mode that defeats a correctly rated CT. When the fault current, multiplied by the per-unit burden, pushes the secondary EMF past the knee-point voltage, the core saturates and the secondary current no longer tracks the primary; a differential relay then sees a false operating current during an external fault. IEEE C37.110-2023 gives the screening relation where fault current in CT-rated units times the per-unit burden, scaled by (1 + X/R), must stay below the knee-point or C-rating headroom — a check that catches the low-voltage CT on a large transformer that looks fine on steady-state current yet saturates within the first cycle of an offset fault.

A wiring diagram of a CT secondary loop from the CT to the meter and relay burden
Figure 5 — Every element in the S1–S2 loop adds burden; the lead resistance is usually the largest controllable term.
A fault tree from high fault current through burden and X/R to CT saturation and relay misoperation
Figure 6 — Saturation is rarely one cause; it is fault current, burden and X/R converging on a core driven past its knee point.

Boundary and limitations

First, the chart assumes the load current you measured is the load current that will occur, and a future plant expansion that lifts the peak by a third quietly moves the operating point out of the accurate band without changing a single nameplate figure. The chart sizes for today’s load plus headroom, not for the next decade, so the number must be revisited when the feeder is re-rated.

Second, the chart cannot see the lead resistance, which is the term most often underestimated in the field. A burden calculated on the relay’s 0.1 VA and the CT’s own resistance ignores 80 m of undersized cable and lands the real loop well above the rated VA, so the CT saturates under fault even though the paper specification passed. A negative or healthy-looking reading at low current is only a statement that nothing was stressing the core then, not evidence the unit is sound under fault. a CT sized only from ratio and class, with the burden loop left as an afterthought, passes every catalogue check and still misoperates on the first external fault — the three quantities (ratio, class, burden) are one system, and the third is where the failures hide.

Third, the IEC and IEEE dialects are not the same instrument wearing two labels. A 5P20 CT specified by composite error at the accuracy limit factor and a C400 CT specified by terminal voltage at 20× rated can serve one feeder yet give different saturation margins, and substituting one for the other on a differential scheme invites exactly the unequal-performance problem that produces false differential current. on one 30 MVA substation transformer the high-voltage bushing CT and the low-voltage switchgear CT were both “correctly rated” on steady-state current, yet only the low-voltage side saturates on a through-fault because its lead burden was three times the high-voltage side; we caught it on the saturation check, not on the ratio, and re-balanced the loops before commissioning.

Key takeaways

  • A current transformer steps primary current down to a 1 A or 5 A secondary so meters and relays read it without touching the conductor.
  • Size the primary at 1.25 to 1.5 times the maximum load current, then pick the class for each duty and verify the burden fits.
  • The current transformer sizing chart gives ratio, class and burden per application; the burden and saturation checks decide if it survives a fault.
  • Metering classes (0.2S, 0.5S) are accurate at load and saturate early; protection classes (5P, 10P, PX) stay linear into fault current.
  • Match the work to IEC 61869-1:2023 and IEC 61869-2:2017, or to IEEE C57.13-2016 and IEEE C37.110-2023, and keep the measurement standard separate from the application guide.
  • Never leave a CT secondary open while the primary is energised, and never treat the burden loop as an afterthought.

Need a quotation for an instrument transformer tester?

Tell us the equipment you need to test, the voltage class and the quantity. Our engineers reply with a technical proposal and a quotation within 12 hours — English manual, remote video guidance and a one-year warranty on exported units.

Payment terms agreed per order · Lead time confirmed per order

Frequently asked questions

What is a current transformer and why is it isolated?

A current transformer is an instrument transformer that reproduces the primary current at a safe 1 A or 5 A secondary so measuring and protection devices can read a high-voltage circuit without connecting to it. The isolation comes from the magnetic core and insulation between primary and secondary, which is also why the secondary must always stay closed through a burden — opening it while live drives the core into saturation and produces a dangerous overvoltage.

How do I size a current transformer for my load?

Start from the maximum continuous load current and multiply by 1.25 to 1.5 to set the primary rating, choose 1 A or 5 A secondary by cable length, then pick the accuracy class for metering and protection and confirm the connected burden is within the rated VA. A current transformer sizing chart summarises these steps per application, but the burden and saturation checks are what confirm the choice under fault.

What is the difference between metering and protection CT classes?

Metering classes such as 0.2S and 0.5S are precise at normal load and deliberately saturate early under fault to protect the meter, while protection classes such as 5P20 and 10P20 stay linear into many times rated current so the relay sees the fault. The two are wound on different cores in a multi-core CT, and swapping them defeats both the revenue measurement and the protection.

What does the accuracy limit factor mean?

The accuracy limit factor, or ALF, is the multiple of rated primary current at which a protection CT still holds its stated composite error — a 5P20 CT keeps within ±5% composite error (IEC 61869-2:2017) up to 20 times rated. It tells the engineer how far into a fault the CT remains trustworthy, which is the quantity a relay-setting study needs to avoid misoperation during the through-fault.

Why must the CT secondary never be open-circuited?

With the primary energised, opening the secondary removes the demagnetising ampere-turns, so the full primary magnetomotive force saturates the core and induces a hazardous kilovolt-level EMF at every flux reversal. Always short the secondary terminals before disconnecting any burden, and treat an open CT secondary as a live electrical hazard.

Conclusion

Recommended configuration

Shortlist the instruments below and confirm the voltage class and accuracy against your site survey.

FunctionRecommended modelSelection note
PrimaryHF-IT-203 Current Transformer Calibratormatched to your voltage class
ComplementaryHF-IT-205 Wireless CT Ratio Testerroutine and acceptance testing

A current transformer sizing chart is the fastest way to turn a load study into a defensible CT specification, but the chart only earns its place when the engineer also checks the burden loop and the saturation margin that the chart cannot see. Size from the load, pick the class for the duty, and verify the connected VA and the knee-point or C-rating against the real fault current and X/R. Match the measurement to IEC 61869-1:2023 and IEC 61869-2:2017, or to IEEE C57.13-2016 and IEEE C37.110-2023, and keep the standard separate from the application guide. Pair the CT with a calibrated test set so the nameplate claims are verified before the breaker closes, and the measurement becomes evidence rather than assumption.

Explore related instrument transformer test equipment

If you are specifying or verifying CTs on a particular feeder, the Instrument Transformer Tester range covers the instruments that confirm a nameplate in the field. Four from that range are worth comparing before you commission:

Our full guide to the instrument transformer range explains how these instruments work together inside a substation or plant maintenance plan, and the instrument transformer range covers the complete set.

Contact our engineering team for a CT specification review sized to your site, or request a datasheet for the units above.