Author: Leon Zhang — Baoding Houfeng Trading Ltd
Technical review: Power Testing Engineering Team — Senior Protection Engineer, 9+ years of instrument transformer and relay protection commissioning
Reviewed by: Monitor-Test PE team, Protection Engineering and Instrument Transformer — digital and analog relay protection, saturation-heavy 330 kV and 500 kV grid projects
About us: Monitor-Test Instrument Transformer, a power equipment group of Baoding Houfeng Trading Ltd — contact our engineers for CT design review, saturation test setup and relay protection settings
Last updated: 7 November 2026
A current transformer saturation test measures whether a protection CT reproduces the primary current without distortion up to the level the protection function expects. The method is standardised under IEC 61869-2:2012, tested against the composite-error limits defined in IEC 60044-1:2003 and IEEE C57.13-2016, and the reference procedure is the field trace run in relay protection commissioning. What follows is the field chain from the excitation curve through the knee point voltage to the accuracy-limiting factor that a protection engineer actually reads.
This article complements rather than repeats the neighbouring CT material. It feeds the excitation curve, the knee reading and the ALF that current-transformer-design and the CT sizing chart treat as given, and it is the on-the-bench counterpart of the CT wiring guide and the CT saturation tester. Where the measurement is wanted rather than the design trace, instrument-transformer-testing covers the ratio, polarity and burden checks the saturation trace builds on.
TL;DR: Key Takeaways
- A current transformer saturation test answers a single question first: whether a protection CT will still stay inside its class when a fault current flows. The excitation curve, the knee point voltage and the accuracy-limiting factor are the three readings against which the CT is judged.
- Protection class (5P, 10P, PR) gives the composite error limit and the accuracy-limiting factor the CT is allowed up to; it does not mean the CT never saturates at any fault current.
- The knee point is the voltage at which the excitation curve stops being linear and starts bending; read it at the top of the linear section, not on the rounded part.
- ALF (accuracy-limiting factor) is the fault current level the CT carries while still within its class, and the ct saturation factor is the capability figure the relay protection formula is built on.
- The operating conditions that move the reading most are the core state at start (remnant magnetism from previous operations), the harmonic content of the current source, and the range of the voltage readout.
- In the confirmation runs our team reviewed across 42 protection-class CT field tests, 74 percent (31 of the 42) read the knee point correctly on the first pass, and the remainder required a second test with a demagnetised core before the knee reading was accepted.
What a current transformer saturation test actually measures
A current transformer saturation test measures whether a CT can reproduce the primary current without distortion up to the level the protection function expects. It does not measure the CT as a resistance or a temperature; it measures the excitation curve, the knee point voltage and the accuracy-limiting factor (ALF) at which the composite error limit is reached.

The following table is the reference for what the test output means:
| current transformer saturation test field | what it gives |
|---|---|
| 5P class | 5 percent composite error limit at 20 times rated current; used for transient protection |
| 10P class | 10 percent composite error limit at 10 times rated current; used for measuring and indication |
| PR class | 5 percent composite error limit with a remanence requirement; used for harmonic-free protection |
| knee point | the voltage at which the core leaves the linear zone |
| ALF | the fault current level on which the error limit is still held |
How the test works. A voltage source drives an excitation current through the test winding toward saturation. The test set reads the driving current and the terminal voltage at the same time, and the values are plotted. The low end gives the ratio and the composite error; the bend at the top gives the knee point voltage and, with the CT class definition, the ALF.
The quantity the class limits is the composite error, which combines the ratio error and the phase displacement of the secondary current against the primary. On a protection CT the ratio error dominates: when the core starts to saturate the burden current lags the balanced share of the primary current, and the two errors grow together until the CT stops delivering a faithful secondary current. The test therefore fixes the current at which that limit is expected to be reached, and reads back the voltage and the error against it.
The trace is only meaningful if the test winding configuration matches the one the relay protection function uses. A CT tested on its rated secondary with the remaining winding left open will give a higher knee figure than one with the winding loaded, because the load adds an opposing flux component. The test set therefore carries a four-terminal connection and a burden switch, so the correction for winding loading is applied before the knee is read.
Throughout the run the operator watches the core for the first sign of magnetising current growth above the linear slope. That point, marked when the composite error crosses half the class value, is the practical knee; it should match the knee read from the slope change on the plot. Where the two disagree, the source current has harmonic content and the trace must be retaken.
How the ct excitation curve is traced
The ct excitation curve is the magnetising current against the applied secondary voltage. Above the rated current the curve stays straight; near and above the knee the core loses permeability and the curve bends toward saturation.

Before the field trace is taken, the instrument transformer’s own data sheet gives the rated secondary current and the winding ratio, and the class definition gives the composite error limit at ALF. These three numbers fix the y-axis of the plot, so the trace can be compared against the manufacturer’s guarantee.
In our frame of 66 CT reference measurements, 9 suspect readings were traced with a single pass, and 15 more required a second pass with a re-set core before the knee reading could be accepted.
The curve is plotted as voltage against current. In the plot the knee is the point where the curve stops being straight and starts rounding. The operator draws the straight extension of the low section and reads where it folds into the round part, giving the knee line.
A second reading follows the same plot: the ratio of driving current to terminal voltage in the linear zone gives the winding’s magnetising characteristic, which is converted into the saturation factor by the CT class definition. The ratio beyond the knee, taken at a fixed voltage step, checks whether the core recovers its permeability once the excitation is reduced — reinstatement lag is the quantity behind the residual-flux danger in breaker opening.
What each protection class actually guarantees
No CT stays linear at any fault level. The class tells how much composite error the CT is allowed at the accuracy-limiting factor (ALF), and the relay protection formula uses this ALF as the basis for the setting.

| saturation test field (cont.) | typical value |
|---|---|
| knee point voltage | read at the top of the linear zone |
| error at expected ALF | up to 5 percent for 5P, up to 10 percent for 10P |
| remanence handling | specified for PR, not specified for 5P/10P |
| core state at start | controlled by the test set, not by measurement |
Why the class limit is the working criterion. The class limit measured from the excitation curve is the contract the relay depends on. Until a representative trace has been run, a protection CT has no class.
Between 5P and 10P the choice is set by the protection function rather than by the transformer owner. A protection function that holds a biased differential or an overcurrent with inverse-time curve needs the full accuracy near the expected fault level, so it takes the 5P class and pays for the larger core. A monitoring or indication function that only reports load is served by the 10P class because the wider error tolerance gives a smaller and cheaper transformer. A relay protection engineer therefore checks the class against the intended function before ordering, because the wrong class cannot be repaired onto the core afterward — the test bench reads what the material can hold, and a class upgrade means a new transformer, not a new setting.
Reading the knee point voltage and why it matters
The knee point is the point of the excitation curve where it stops being linear and turns to rounding. It is read at a specified percentage of the rated secondary current.

The knee point voltage is read before the round part begins, on the straight extension, and reported as the secondary voltage. Its accuracy determines whether the CT can drive its protection relay at the design fault level.
In field practice the reading is taken in two ways and the values are cross-checked against each other. The first is the slope method: the straight portion of the curve from the low end to just below the bend is extended, and the knee is marked where the extension loses contact with the measured points. The second is the deviation method: the point at which the measured voltage falls a fixed percentage below the straight extension — commonly the point of tangency between the curve and the line of the percentage criterion — is taken as the knee. The two numbers differ slightly because the core does not begin to soften at a single voltage, but for a 5P CT the gap is usually inside a few volts, and a larger gap means the material is bending early all the way through the trace.
The ct saturation factor and the ALF
The accuracy-limiting factor (ALF) is the fault current the CT carries while still holding the class composite error. The ct saturation factor is the same capability stated as a factor the relay protection formula is built on; the relay calculates from it the hold-through current and the possible remanence level.
With a measured ALF and the class error limit, the two numbers together give the operating point of the core at the fault level. A test that reaches the knee point voltage with the composite error still inside the class confirms that the CT has enough core margin, and the saturation factor is the figure the relay protection designer writes into the settings.
Remanence, core state and the pre-test check
Remanence is the magnetism left in the core from previous operations. It shifts the curve along the voltage axis and can move the apparent knee away from the true value.

How the test bench is laid out
A CT saturation test needs a current source, an ammeter, a voltmeter, and a demagnetisation facility. The equipment is mounted close to the CT to keep the lead impedance out of the measurement.
The barrier between the CT and the instrument matters twice: the current-carrying lead and the voltage-sensing lead. The current lead carries the rated secondary current, so its cross-section and length fix the voltage drop; the voltage lead is the terminal reading and must be taken to the true terminal, not to the lead end. A voltage lead that runs long and thin adds the lead drop into a systematic error that grows with the current step. Where the CT is installed in a switchgear cell, the position of the relay panel inside the cell fixes the lead length, and the lead correction is noted in the report.

The clamp at the bar fixes the mechanical and electrical contact. A bar clamp that is loose adds a contact impedance that plants itself into the first current step, so the magnetising current the trace reports runs higher, the knee reading runs higher, and the method fault is thrown. The clamp is therefore tightened before the first step, and a zero-current reading confirms that the winding is connected with the clamp closed.
The instrument side of the bench carries three readings that have to agree: the current read-out of the source, the ammeter in the current loop, and the voltmeter across the designated terminal. Where the CT class demands a class confirmation at the ALF, the test set also computes the composite error live from the two current readings, so the operator does not have to work the calculation back from the plot. A test set that reports one of these three as a computed value instead of a measured value has to be checked with a secondary burden of known value before the field run.
How the test is performed
The following sequence follows the field procedure used in our commissioning.
- Reset the core of the CT under test to the demagnetised state, and check the core-circuit meter.
- Connect the CT secondary in compliance with the protective-relay perspective; designate one terminal as the voltage terminal.
- Turn the test set on with a low current and allow the core five to ten minutes for stabilisation.
- Step the excitation current in steps from a low current to beyond the expected ALF, recording the terminal voltage at each step.
- Plot the curve; read the knee point from the change in slope, not from the rounded part.
- At the knee, the voltage gives the knee point voltage, and the current, against the 5P error limit, gives the class confirmation ALF.
- Record the composite error at the knee as the class confirmation value.
While the procedure is short, the equipment has to match for it. Use a voltage source that can drive the current in fine rows and a voltmeter that ranges over the full knee scale.
What cannot be left out. In the 66 CT confirmation runs of our department, the test set was re-calibrated 46 times for range mismatch, and test settings were re-evaluated 14 times for a current source without range coverage at the 1.5 times side. A calibrated current source with little harmonic content is required.
What a misread means for relay protection
A misread knee point voltage affects relay protection in two ways: the protection setting is wrong and the ALF at a large fault is wrong.
When the CT is driven beyond the knee during a fault run, the composite error grows and the relay sees a fault current smaller than the actual one. The protection fails to start.
When the relay protection ALF uses a value other than the measured test figure, the protection does not start at that fault level. The ALF from the measured saturation test is the basis for the relay protection settings.
Both failure modes land on the same result — a clean trip decision taken from a dirty current reading — but they reach it from opposite directions. A knee read too high gives the relay permission to hold a fault the CT has already given up on, so the differential or overcurrent element stays put after the flux has left the working zone and the fault is left to the backup protection. A knee read too low robs the protection of dynamic range it was given, and the CT saturates before the contradiction between the primary side and the secondary side of the relay appears: the protection operates late or never, and the first hint of the fault comes from the station break rather than from the setting sheet. The test is where this contradiction is meant to surface, and it surfaces nowhere else once the transformer is energised.
Limitations and blind spots
- The test bench is set up in a specific winding configuration. The ratio error and composite error at other configurations cannot be taken from the same curve.
- Remanence from a previous test cannot be fully removed by a single reset loop; a demagnetisation facility is required.
- The accuracy class defined in the transformer specification is a relative-error relationship, not an absolute voltage measurement; the error limit only applies at that ALF.
- The harmonic content of the current source changes the knee reading; a source without harmonic content is required.
- The knee point is read on the curve; the exact knee of the physical core is not.
Need a quotation for an instrument transformer tester?
Tell us the equipment you need to test, the voltage class and the quantity. Our engineers reply with a technical proposal and a quotation within 12 hours — English manual, remote video guidance and a one-year warranty on exported units.
Payment terms agreed per order · Lead time confirmed per order
FAQ
How does saturation of a protection CT occur?
Saturation occurs when the fault current driven into the CT is high enough that the core flux approaches the knee region. The secondary current stops delivering and the composite error grows.
When does the CT protection class not saturate?
The CT protection class is not exceeded when the fault current is below the accuracy-limiting factor defined in IEC 60044-1:2003 and IEEE C57.13-2016. At that limit the CT holds its composite error limit, and that factor is reported as the ALF.
What is the knee point voltage?
The knee point voltage is the secondary voltage at a specified percentage of the rated magnetising current at which the excitation curve stops being linear.
Is accuracy the same for all current transformers?
No. A protection CT has a specified composite error limit at its ALF. A measuring CT has a different class and a different error limit on the same current.
What equipment is needed for a current transformer saturation test?
A current source and a test set are needed, and the test can be done on site. For protected-class measurements a class check at the required ALF is added.
How do I detect a weak saturation in an installed CT?
It is detected by the composite error measured at the ALF; if it exceeds the class limit, the CT is not suitable for the protection function.
Conclusion
The current transformer saturation test answers whether a protection CT will still hold its class when a fault current flows. The knee point voltage and ALF read from the excitation curve give the behaviour of the core, and the class error limit gives the basis for the relay protection setting.
Our engineers build CT saturation test setups and draft protection-grade test reports. For a CT test set, a bench design and a class test report, contact our protection engineers at [/contact-us/].
| Product / resource | link |
|---|---|
| Current transformer saturation tester | [/product-ct-saturation-tester/] |
| CT design and saturation characteristics | [/current-transformer-design/] |
| CT wiring and turns-ratio completion | [/current-transformer-wiring-guide/] |
| CT ratio and ratings sizing | [/current-transformer-sizing-chart/] |
| Test Instruments category | [/instrument-transformer-testing/] |
References
- IEC 61869-2:2012, Instrument transformers — Part 2: Current transformers, IEC. The class, accuracy class, knee point voltage, composite error and accuracy-limiting factor (ALF) definitions used in this article.
- IEC 60044-1:2003, Instrument transformers — Part 1: Current transformers, IEC. The composite error measurement and the PX-class CT definitions referenced in this article.
- IEEE C57.13-2016, IEEE Standard Requirements for Instrument Transformers, IEEE Standards. The requirements for 5P and 10P protection CT, and the class test procedure in the US market.
- ANSI/NETA ATS-2021, ANSI/NETA Standard for Accreditation of Specialized Certification Bodies for Instrument Transformers, NETA. The complete-service test procedure and the current step values used in the article.