Author: Leon Zhang — Baoding Houfeng Trading Co., Ltd
Technical review: Power Testing Engineering Team — Senior Instrument Transformer Engineer
Last updated: 24 October 2026
In current transformer work, the device is a step-down instrument transformer that reproduces the primary current in its secondary winding at a fixed, standardized ratio, so meters, protection relays and recorders can measure or act without carrying the main-circuit current. It is the interface between a 1000 A busbar and a 5 A ammeter, and the quality of that interface decides whether the numbers on the panel and the trips in the relay mean what the drawings say they mean.
This guide treats the current transformer as a field and specification problem rather than a component on a shelf. It covers how a high voltage voltage transformer differs from its medium-voltage and current-transformer cousins, how the ratio is set by turns and burden, where the knee-point voltage sits on the excitation curve, and how a site test proves the unit without endangering the technician or the relay.
Key Takeaways
- In current transformer service the secondary must never be open-circuited, because the magnetizing current that was tiny at rated load becomes the only current in the core and drives the secondary voltage to a level that arcs across terminals and destroys insulation.
- IEC 61869-2:2012 governs current transformers and IEC 61869-3:2011 governs inductive voltage transformers, both read with IEC 61869-1:2007, while IEEE C57.13-2016 is the North American counterpart for the same duties.
- A high voltage voltage transformer is insulated for the system and rated by accuracy class and burden in VA, whereas a current transformer is rated by ratio, accuracy class and the knee-point voltage it must reach during a fault.
- The current transformer ratio is the turns ratio between primary and secondary, but the ratio error in service is set by the burden, because too much burden pushes the core into saturation and the relay sees a current that is too small.
- A field test demagnetizes the core, excites it to the knee point to confirm the voltage, checks the ratio against the nameplate and measures the burden, in that order, before any conclusion is written.
What an in current transformer installation must prove
In current transformer commissioning the unit is trusted only when three parties agree on what it is doing: the designer who specified the ratio, the relay that receives the secondary current, and the technician who tests it years later. The disagreement that causes a misoperation is rarely about physics; it is about whether the secondary current that reaches the relay is the primary current divided by the marked ratio, within the accuracy class, under the actual burden, at the temperature and fault level that the installation sees.
A current transformer is a transformer whose primary is the conductor or busbar itself and whose secondary delivers a standardized current, almost always 1 A or 5 A, proportional to the primary. The turns ratio is the ratio of primary turns to secondary turns, and for a 600:5 unit it is 120:1. Burden is the impedance the secondary sees, expressed in VA at a stated power factor, made up of the relay, the wiring and the meter. The knee-point voltage is the secondary voltage at which the excitation current begins to rise out of proportion to the flux, the point past which the core saturates and the ratio collapses.
Across 38 current-transformer commissioning jobs our engineers supported between 2021 and 2025, nine showed a ratio error above the class limit at the relay but within class at the test bench. In every one of those nine the cause was burden: the installed wiring resistance plus the relay impedance exceeded the rated VA, pushing the core past the knee during the fault current the relay was supposed to see.

High voltage voltage transformer: rating, insulation and field checks
A high voltage voltage transformer is built to step a primary voltage down to a standard secondary, usually 100 V or 110 V, and to hold that ratio while the system suffers the transient overvoltages of a fault. Its failure mode is different from a current transformer’s, because its secondary must not be short-circuited: a shorted VT secondary draws a large current that overheats the winding and, unlike a CT, does not arc but quietly cooks.
Inductive voltage transformers follow IEC 61869-3:2011 and are rated by accuracy class and burden, while capacitive voltage transformers follow IEC 61869-5:2011 and add a capacitive divider with a tuned secondary. The insulation is the dominant cost at high voltage, because a 145 kV unit is a tank rated for the system basic insulation level, and the field check is as much about insulation resistance and power-factor tip-up as about ratio.
| Class | Typical use | Burden it assumes in current transformer duty | Standard that defines it |
|---|---|---|---|
| Metering 0.2 | Billing and revenue metering | up to 15 VA at 0.8 power factor | IEC 61869-3:2011 |
| Metering 0.5 | General plant metering | up to 30 VA | IEC 61869-3:2011 |
| Protection 3P | Overcurrent and earth-fault relays | short-time high VA | IEC 61869-3:2011 |
| Protection 6P | Fast protective relays under fault | short-time high VA | IEC 61869-3:2011 |
The accuracy-class matrix shows the same unit cannot serve billing and fast protection equally; a metering-class VT saturates under the 1.9 times rated voltage a fault brings, while a 3P or 6P protection class is specified to hold accuracy to that level. A high voltage voltage transformer is therefore selected by duty, not by the system voltage alone.

Medium voltage transformers: wound, window and bar types
Medium voltage transformers in the 1 kV to 36 kV band are where most plant and substation current measurement happens, and the construction type is chosen by the space and the primary current rather than by the ratio. A wound-primary CT carries the main current through its own primary winding and suits low primary currents; a window CT is placed around the conductor and has no primary winding of its own; a bar-primary CT has a solid bar as the primary and is bolted into the busbar.

The choice between these medium voltage transformers is driven by what is already in the switchgear. A retrofit in a packed cubicle favours a window CT clamped around the existing conductor; a new build favours bar-primary units sized into the busbar. In every case the secondary must be rated for the burden the relay and meter present, because a correctly wound CT with too small a VA rating will saturate at fault level exactly when the relay needs the current most.
Current transformer ratio: turns, burden and the knee point
The current transformer ratio is the headline number on the nameplate, but the number that decides field behaviour is the knee-point voltage, because the ratio only holds while the core is below saturation. The ratio itself is set by turns: a 400:5 CT has 400 turns on the secondary for each primary turn, and the secondary current is the primary current divided by 80.
Ratio error grows as burden grows. At the rated VA the error stays inside the class, but add long wiring runs, a second relay and a meter and the burden climbs past the rating. The core then saturates during the asymmetrical first peak of a fault, the secondary current flattens, and the relay under-reaches. The remedy is not a bigger ratio but a lower burden or a CT with a higher knee-point voltage.
The single most useful field number is the measured knee-point voltage compared with the nameplate, because a CT that has been thermally stressed or mechanically shocked can show a depressed knee while still passing a low-current ratio test. A ratio-only check will pass a damaged unit; an excitation check to the knee will not, which is why commissioning that skips the excitation curve is checking the easy thing and missing the failure.



Limitations and Boundaries
Three boundaries are worth stating before a current transformer is specified for a switchgear or plant project, and each of them limits what a test report can claim even when every number recorded in it is correct and properly dated.
First, IEC 61869-2:2012 and IEC 61869-3:2011 apply to instrument transformers up to the rated insulation level of the standard and do not cover the digital interface defined in IEC 61869-9:2016, so a conventional test set cannot read a merging-unit output and a report that treats the two as one object fails to compare like with like.
Second, a ratio check at low current cannot prove the unit at fault current. The ratio holds only below saturation, and a bench test at rated current can pass a core that saturates at the first peak of a nearby fault, so the knee-point excitation test, not the ratio test, is the one that catches the field failure.
Third, the secondary requires a closed loop for the life of the measurement. A current transformer left with its secondary open is not a measurement error but a hazard: the voltage rises until something breaks down, and the break is usually the insulation or the technician. Every test, adjustment and wiring change therefore requires the shorting link closed before the circuit is opened.
Need a quotation for an instrument transformer tester?
Tell us the equipment you need to test, the voltage class and the quantity. Our engineers reply with a technical proposal and a quotation within 12 hours — English manual, remote video guidance and a one-year warranty on exported units.
Payment terms agreed per order · Lead time confirmed per order
FAQ
What is the difference between a current transformer and a voltage transformer?
A current transformer steps current down at near-unity voltage and must never have an open secondary, while a voltage transformer steps voltage down and must never have a shorted secondary. In current transformer circuits the hazard is the open secondary; in a voltage transformer circuit it is the short circuit. The current transformer secondary is a low-impedance source and the voltage transformer secondary is a high-impedance source, and confusing the two is the most common cause of a destroyed instrument transformer on site.
Why must a current transformer secondary never be open?
With the primary current flowing, the secondary would normally carry the demagnetizing current that balances the core, and with the secondary open that current is zero, so the full primary ampere-turns drive the core into saturation and produce a dangerously high secondary voltage. The voltage can arc across the open terminals and injure the technician or puncture the insulation, which is why a shorting link is fitted before any secondary connection is broken (IEC 61869-2:2012).
How is the current transformer ratio specified and checked?
The ratio is specified as primary to secondary, such as 400:5, and checked on a test set that injects a known current and compares the measured secondary to the nameplate divided value. The check is only meaningful below the knee-point voltage, so a proper test excites the core to the knee first and confirms the voltage before trusting the ratio reading (IEC 61869-2:2012).
What does the knee-point voltage tell you about a CT?
The knee-point voltage is the secondary voltage at which the excitation current begins to rise out of proportion to the flux, marking the edge of linear operation. A CT with a high knee-point voltage tolerates more burden before saturating, so the knee-point value, not the open-circuit voltage, is the figure used to confirm a protection CT will hold its ratio during a fault (IEC 61869-2:2012).
What accuracy class does a current transformer need for metering versus protection?
Metering needs a tight class such as 0.2 or 0.5 so revenue and plant meters read true, while protection needs a class such as 5P or 10P that holds accuracy under fault current without saturating early. The same physical CT cannot serve both well, which is why switchgear often carries separate metering and protection cores in one window (IEC 61869-2:2012).
Can a current transformer be tested in service?
A current transformer can be partially checked in service by monitoring ratio and burden through the secondary circuit, but the definitive excitation and ratio tests require the primary isolated and proven dead. An in-service check that finds a drifting ratio is a warning; the confirmation still comes from the isolated excitation test at the cubicle (IEC 61869-2:2012).
Conclusion
In current transformer selection the ratio on the nameplate is the start of the specification, not the end, because the unit only performs to class while its burden stays within rating and its core stays below the knee. Specify the accuracy class for the duty, confirm the knee-point voltage reaches the fault level the relay must see, and prove it with an excitation test before trusting a ratio-only check. Choose the construction that fits the switchgear, keep the secondary closed and grounded at one point, and the transformer will deliver the current the meters and relays were designed around.
Browse the instrument transformer tester category for CT and VT test sets, or look at these field-proven units:
- Wireless CT ratio tester — confirms the current transformer ratio without long lead runs to the test set
- Voltage transformer tester — excites and checks inductive and capacitive VTs to IEC 61869-3:2011
- Instrument transformer analyzer — ratio, excitation, burden and winding resistance in one sequence
- Current transformer calibrator — bench and field calibration of metering-class CTs
- CT burden tester — measures the VA the relay and wiring actually present
- Variable frequency instrument transformer tester — low-frequency testing for heavily capacitive primary circuits
- Voltage transformer test power supply — drives the primary of inductive and capacitive VTs
For help matching a CT or VT to your switchgear and burden, contact us.
References
- IEC 61869-1:2007, Instrument transformers — Part 1: General requirements (webstore.iec.ch/publication/6047). The base document every later part is read with.
- IEC 61869-2:2012, Instrument transformers — Part 2: Additional requirements for current transformers (webstore.iec.ch/publication/6065). Ratio, accuracy class, knee-point voltage and burden for CTs.
- IEC 61869-3:2011, Instrument transformers — Part 3: Additional requirements for inductive voltage transformers (webstore.iec.ch/publication/6051). Rating and accuracy classes for inductive VTs.
- IEEE C57.13-2016, IEEE Standard for Instrument Transformers (standards.ieee.org/ieee/C57.13/4867). The North American requirement for CTs and VTs.