HF-RT-209 Two-clamp Phase Angle Tester
This two-clamp phase angle tester is designed for three-phase power commissioning. It accurately tests phase angle, phase sequence, voltage and current without disconnecting wires, widely used in substation wiring check and power circuit troubleshooting.
Send your requirements, we will quote for you within 12 hours
Product Features
● It adopts clamp-on current transformers for current input, so no need to disconnect the tested circuit during measurement.
● Fully insulated isolation is designed between the two input channels when measuring the phase difference between U1 and U2, completely preventing circuit short-circuits and instrument burnout caused by incorrect wiring.
● Equipped with a high-contrast LCD screen with 25 mm large characters, delivering excellent viewing experience.
● The housing is made of insulated engineering plastic, ensuring high safety and reliable performance.
Technical Parameters
Basic Error Limits
AC Voltage (See Table 1)
| Range | Resolution | Basic Error Limit |
|---|---|---|
| 20 V | 0.01 V | ±(0.3% reading + 0.2% full scale) |
| 200 V | 0.1 V | |
| 500 V | 1 V |
AC Current (See Table 2)
| Range | Resolution | Basic Error Limit |
|---|---|---|
| 200 mA | 0.1 mA | ±(0.3% reading + 0.2% full scale) |
| 2 A | 1 mA | |
| 10 A | 10 mA |
Phase Measurement (U-U, U-I, I-I, See Table 3)
| Measuring Range | Resolution | Basic Error Limit |
|---|---|---|
| 0 ~ 360° | 1° | ±2° |
Operating Errors
| Category | Parameter | Value |
|---|---|---|
| Rated Operating Conditions | Ambient Temperature | (0 ~ 40) °C |
| Ambient Humidity | (20 ~ 80) % RH | |
| Measured Signal Waveform | Sine wave, β=0.05 | |
| Measured Signal Frequency | (50±0.5) Hz | |
| Position of measured conductor inside clamp jaw | Arbitrary | |
| Amplitude Range of Measured Signals for Phase Test | Phase measurement between U1-U2 | 30V ~ 500V |
| Phase measurement between I1-I2 | 10mA ~ 10.00A | |
| Phase measurement for U1-I2 / I1-U2 | 10V ~ 500V, 10mA ~ 10.00A | |
| External power frequency electromagnetic interference | To be avoided | |
| Rated Operating Error Limit | Under specified rated working conditions, the operating error limit for each measurement shall not exceed twice the corresponding basic error limit. |
Safety Characteristics
| Item | Specification |
|---|---|
| Withstand Voltage | The device can withstand 1000V/50Hz sinusoidal AC voltage for 1 minute between voltage input terminals & casing, and between clamp CT iron core/clamp jaw & internal windings; 500V/50Hz sinusoidal AC voltage for 1 minute between two voltage input terminals. |
| Insulation Resistance | ≥ 10 MΩ between internal circuits and casing, and between two voltage input terminals. |