HF-RT-201 6 Phase Relay Test set

This 6 Phase Relay Test set supports comprehensive Protective Relay Testing. It outputs six independent voltage and current sources to simulate complex grid faults, accurately calibrate all types of protection relays complying with IEC and ANSI criteria for power substations.

Send your requirements, we will quote for you within 12 hours

  • TEL: +86 13655813266
  • Whatsapp: +86 13655813266
  • zxl635973785@gmail.com

Features & Main Functions

  1. Tailored for field test requirements, this unit provides standard 6-phase voltage and 6-phase current outputs. It can test traditional relays, protection devices and modern microprocessor-based protection equipment, especially ideal for transformer differential protection and backup protection tests with enhanced convenience and completeness.
  2. It complies with GB/T 7261 Basic Test Methods for Relay Protection and Safety Automatic Devices and DL/T 624-2010 Technical Conditions for Microcomputer Relay Protection Test Devices.
  3. Equipped with classic Windows XP system, it boasts friendly HMI for easy operation. The high-performance embedded industrial controller paired with a 10.4-inch 800×600 TFT true-color screen displays abundant data including operating status and fault messages.
  4. The built-in system recovery function avoids system breakdown caused by illegal shutdowns or misoperations.
  5. The front panel has ultra-thin multifunctional shortcut keys and an optical mouse; users can operate the device via keyboard and mouse just like a regular PC.
  6. Its main control board adopts DSP+FPGA structure with 16-bit DAC output, generating high-density sine waves of 2000 points per cycle, which greatly improves waveform quality and testing precision.
  7. The high-linearity power amplifier guarantees both tiny current accuracy and stable large current output.
  8. A USB port enables direct PC connection without adapter cables for convenient wiring.
  9. Laptops can be connected for operation; laptops and the built-in controller share identical software with no extra learning needed.
  10. Independent dedicated DC auxiliary power outputs are available: 110V (1A) and 220V (0.6A), supplying working power for relays and protection devices requiring DC power supply.
  11. The built-in automatic software calibration function eliminates manual potentiometer adjustment for accuracy calibration after startup, greatly improving equipment stability.

Technical Specifications

AC Current Source (6*30A)

Parameter Specification
Single-phase current output (RMS) 0~30A per phase, accuracy: 0.2% ±5mA
6-phase parallel output (RMS) 0~180A, six phases parallel with identical phase
Long-term permissible operating current per phase (RMS) 9.9A
Max output power per phase 320VA
Max total output power for six parallel currents 1800VA
Max allowable working time for combined six currents 5s
Frequency range 0~1000Hz, accuracy: 0.01Hz
Harmonic order 2~20 orders
Phase 0~360°, accuracy: 0.1°

DC Current Source

Parameter Specification
DC current output 0~±10A per phase, accuracy: 0.5% ±5mA

AC Voltage Source

Parameter Specification
Single-phase voltage output (RMS) 0~120V per phase, accuracy: 0.2% ±5mV
Line voltage output (RMS) 0~240V
Phase/Line voltage output power 75VA / 100VA
Frequency range 0~1000Hz, accuracy: 0.01Hz
Harmonic order 2~20 orders
Phase 0~360°, accuracy: 0.1°

DC Voltage Source

Parameter Specification
Single-phase voltage peak output 0~±160V, accuracy: 0.5% ±5mV
Line voltage peak output 0~320V
Phase/Line voltage output power 90VA / 180VA

Switch Terminal Block

Parameter Specification
Digital input terminals 8 pairs
Idle contact 1~20mA, 24V built-in power supply inside device
Potential reversal Passive contact: low-resistance short-circuit signal
Active contact: 0-250V DC/AC
Digital output terminals 4 pairs, idle contacts; breaking capacity: DC:0-30V/5A, AC:0-250V/5A

Others

Parameter Specification
Time range 1ms~9999s, measurement accuracy: 1ms
Overall dimension & weight 418×363×208mm, approx. 17.8Kg
Power supply AC220V±10%, 50/60Hz, 10A

AC Current Operating Duration

Operating Current Allowable Working Time
Operating current < 10A ≤60 minutes
10A < Operating current ≤ 20A ≤70 seconds
20A < Operating current ≤ 30A ≤15 seconds
Operating current: 30A ≤5 seconds

Packing List for 6 Phase Relay Test Set

Item No. Description Qty Unit Remarks
1 6 Phase Protective Relay Test Set Main Unit 1 Set Core host equipment
2 AC220V Power Supply Cord 1 Pcs For mains power connection
3 6-channel Current Output Test Lead Assembly 1 Set Complete current testing wiring
4 6-channel Voltage Output Test Lead Assembly 1 Set Complete voltage testing wiring
5 Digital Input & Output Signal Cable Set 1 Set For switch signal connection
6 DC Auxiliary Power Wiring Harness 1 Set For 110V/220V auxiliary power output
7 USB Communication Cable 1 Pcs Connection between host and computer
8 Keyboard & Optical Mouse 1 Set On-site operation control
9 Software Installation CD + Manual USB Flash Drive 1 Set Operating program & electronic documents
10 English Printed Operation Manual 1 Copy Official operation guide
11 Factory Calibration Certificate 1 Copy ISO recognized calibration document
12 Factory Quality Inspection Report 1 Copy Pre-delivery quality test record
13 Spare Fuses Pack 1 Pack Consumable spare parts
14 Export Shockproof Wooden Case 1 Pcs Foam inner lining, for sea/air transportation

FAQ: 6 Phase Relay Test Set

Q1: What is a 6 Phase Relay Test Set mainly used for?

A1: It performs comprehensive Protective Relay Testing. With 6 independent voltage & current channels, it simulates various grid faults to calibrate transformer differential protection, backup protection, RMU relays and all types of microcomputer-based substation protection devices, complying with IEC and ANSI standards.

Q2: Which industry standards does this tester comply with?

A2: It meets GB/T 7261, DL/T 624-2010 national standards, and fully adapts to international IEC & ANSI protection testing specifications for global power system projects.

Q3: What is the maximum output current of each channel? Can six phases work in parallel?

A3: Single phase output range: 0~30A RMS. Six phases can be paralleled to reach a total output current up to 180A for high-current testing scenarios.

Q4: How long can the device continuously output rated large current?

A4: Continuous working duration is limited by output current:
<10A: up to 60 mins; 10~20A: ≤70s; 20~30A: ≤15s; 30A full load: only 5 seconds max to protect the power amplifier.

Q5: Does the tester support harmonic and phase angle adjustment?

A5: Yes. It generates 2~20 orders of harmonics, phase angle adjustable from 0° to 360° with 0.1° precision, frequency range 0~1000Hz for flexible fault simulation.

Q6: Is there built-in auxiliary DC power supply for protection relays?

A6: Equipped with two independent DC auxiliary outputs: 110V/1A and 220V/0.6A, which can power field protection devices without an extra external power source.

Q7: What operating system does the tester adopt? Can I connect a laptop to operate it?

A7: Built-in Windows XP embedded system with touch screen, keyboard and mouse. You can also connect an external laptop via USB cable; both devices use identical control software.

Q8: Does the device need regular manual calibration to guarantee accuracy?

A8: No manual potentiometer adjustment required. It has built-in automatic software calibration function to maintain long-term testing precision and stability.

Q9: What communication interface is available between the host and PC?

A9: Standard USB interface, plug-and-play, no extra adapter cables needed for convenient data transmission and program control.

Q10: Can this tester test transformer differential protection (87T) and locked rotor protection (ANSI 48)?

A10: Absolutely. The 6-phase output design is specially optimized for transformer differential protection testing, and fully supports motor locked rotor, overcurrent, under/over voltage, anti-islanding and all common relay protection functions.

Q11: What accessories are included in the standard delivery package?

A11: Complete test leads for voltage/current/switch signals, USB cable, keyboard & mouse, operation software, user manual, calibration certificate, quality report, spare fuses and export shockproof wooden case.

Q12: What is the overall dimension and weight for transportation arrangement?

A12: Dimension: 418×363×208mm, net weight approx 17.8kg, packed in foam-lined wooden case suitable for sea and air freight.

Q13: How to restore the system if misoperation causes system crash?

A13: Built-in one-key system recovery function, which can quickly restore the original system without professional technical support.

Q14: What input power does the tester require?

A14: AC 220V±10%, 50/60Hz, 10A universal mains power supply, applicable to most countries worldwide.

Reviews

There are no reviews yet.

Be the first to review “HF-RT-201 6 Phase Relay Test set”

Your email address will not be published. Required fields are marked *