HF-WC-614 Primary Current Injection Test Set

This compact box-type Primary Current Injection Test Set provides continuously adjustable AC high current output. Widely applied for relay protection calibration, cable temperature rise tests and line fitting thermal cycle experiments. Featuring knob regulation, intuitive control buttons and portable flight case design, it delivers stable current output for on-site power

Send your requirements, we will quote for you within 12 hours​

  • TEL: +86 13655813266
  • Whatsapp: +86 13655813266
  • zxl635973785@gmail.com
Ask an offer now

Product Introduction

High Current Generators are essential equipment for electrical commissioning tasks requiring large current output across all industries. Widely adopted by power plants, substations, electrical manufacturers, scientific research institutions and laboratories, these devices are designed for short-time or intermittent duty cycles.
HF-WC-614 Series High Current Generators are dry-type test transformers featuring low voltage and high current output. They are applicable for current rising tests and load tests on 50Hz circuit breakers, current transformers and other electrical apparatus. Adopting an integrated all-in-one structure, this series enables simple operation and easy data reading, serving as indispensable tools for high-current electrical debugging scenarios. The unit boasts compact size, light weight, reliable performance, as well as convenient operation and maintenance.

Instrument Features

  1. As dry-type transformers delivering low voltage and high current, HF-WC-614 series adapts to current boosting and continuous load tests for 50Hz switches, current transformers and other electrical equipment.
  2. Integrated structure is standard, with high output voltage and strong load capacity. A built-in current transformer facilitates real-time test current monitoring. Models rated above 4000A can be customized into split separate-body structure.

Other Names for the Product

Primary Current Injector, High Current Test Equipment, High Current Test Apparatus, High Current Generator

Technical Parameters

The equipment capacity is designed for a 3-minute short-time working cycle. For intermittent operation, the power-on duration shall be less than 2.5 minutes, and the working interval cycle is recommended to be longer than 10 minutes. Detailed specifications and technical indicators are listed below:
Model & Spec Capacity(kVA) Primary Side Secondary Side Overall Dimension (mm) Weight (kg) Structure Type
V1 (Voltage) A1 (Current) V2 (Voltage) A2 (Current) Output Current
500A 3 200 15 6 500 440×300×550 45 Integrated
1000A 5 200 30 6 1000 500×380×600 78 Integrated
1500A 7.5 200 35 6.5 1500 570×440×750 92 Integrated
2000A 10 200 50 6 2000 570×440×750 105 Integrated
2500A 15 380 40 6 2500 600×430×800
500×400×500
125 Split
3000A 18 380 45 6 3000 300×420×400
500×420×600
80 / 65 Split
4000A 24 380 63 6 4000 640×450×830 180 Split
5000A 30 380 79 6 5000 600×430×880
300×500×500
145 / 120 Split
6000A 36 380 95 6 6000 600×430×880
300×500×500
150 / 140 Split
8000A 48 380 125 6 8000 600×450×950
350×550×550
180 / 160 Split
10000A 60 380 158 6 10000 800×600×1100
380×550×6

Packing List

No. Item Description Qty Unit
1 Main High Current Transformer Host 1 Set
2 Control Panel Cabinet (with regulating knob, start/stop buttons, current display meter) 1 Set
3 High Current Output Connecting Copper Bars / Cables 1 Set Set
4 Power Input Cable 1 Piece
5 Operation & Maintenance Manual (Chinese + English) 1 Copy
6 Factory Calibration Certificate 1 Copy
7 Factory Inspection Test Report (FAT Report) 1 Copy
8 Spare Fuses & Consumable Parts 1 Set
9 Portable Shockproof Aluminum Alloy Flight Case (Integrated type) / Export Wooden Case (Split type above 4000A) 1 Set

FAQ for Primary Current Injection Test Set

Q1: What is this primary current injection test set mainly used for?

A1: It supplies large adjustable AC current to test current transformers, circuit breakers, relay protection devices, and perform temperature rise & load tests for electrical equipment in power plants and substations.

Q2: What working duty cycle does this equipment adopt?

A2: Designed for 3-minute short-time rated operation. For intermittent use, power-on time should be less than 2.5 minutes, with an interval over 10 minutes to avoid overheating.

Q3: What two structural types are available for the YTCDG series?

A3: Integrated all-in-one structure for models below 2000A; split separate-body structure optional for 4000A and higher specifications for easier transportation.

Q4: Why is a built-in current transformer equipped inside the device?

A4: It enables real-time accurate monitoring of output test current, allowing operators to adjust current output conveniently during tests.

Q5: What advantages does the dry-type high current transformer have?

A5: Small volume, light weight, stable performance, no oil leakage risk, simple daily operation and maintenance, suitable for both laboratory and field on-site testing.

Q6: What input power voltage options are available for different models?

A6: Low-current models adopt 200V primary input; specifications of 2500A and above use 380V three-phase industrial power supply.

Q7: Can the output current be continuously adjusted?

A7: Yes. The rotary knob on the control panel realizes stepless current regulation from zero up to the rated maximum output current.

Q8: Is the machine suitable for long-time continuous running?

A8: No. It belongs to short-time/intermittent duty equipment and cannot work continuously for hours, which will cause coil overheating and damage.

Q9: What certificates come with the delivered goods?

A9: Complete accessories include bilingual operation manual, factory calibration certificate, factory inspection FAT report for customer acceptance.

Q10: What packaging is adopted for export shipment?

A10: Integrated machines are packed in shockproof aluminum flight cases; split large-current units are packed in independent export wooden cases with anti-collision foam inside for sea freight.

Q11: What other names do overseas clients call this device?

A11: High Current Generator, Current Booster, Large Current Test Apparatus, Primary Current Injector.

Q12: What industries widely apply this test equipment?

A12: Power grid stations, electrical appliance manufacturers, university labs, scientific research institutes and power engineering construction companies worldwide.

Reviews

There are no reviews yet.

Be the first to review “HF-WC-614 Primary Current Injection Test Set”

Your email address will not be published. Required fields are marked *