Leave your message
- Leon Zhang sales consultant
- Email: zxl635973785@gmail.com
- Phone/WhatsApp/Wechat: +86 13655813266
HF-PQ-204 Harmonic Monitoring
This online harmonic monitoring device monitors fundamental wave and 2-30th voltage & current harmonics in real time. It gives over-limit alarms, uploads data via serial ports and adapts to power systems of various voltage grades.
Send your requirements, we will quote for you within 12 hours
It is widely applied to power supply systems ranging from 380V to 220kV, covering power plants, substations, and large industrial & mining enterprises including petroleum, coal, steel, metallurgy and chemical industries.
Functional Features
- Equipped with premium industrial-grade processor, delivering fast calculation speed, stable operation and excellent anti-interference performance.
- Built-in automatic frequency locking technology ensures accurate analysis results even under grid frequency fluctuations.
- Adopting Fast Fourier Transform (FFT) algorithm, it offers rapid and precise calculation. It routinely monitors fundamental waves, 2~30th harmonic voltage, harmonic current and total harmonic distortion rate (THD) of power circuits.
- Friendly man-machine interface with Chinese display, easy and intuitive operation.
- Able to store up to 60 over-limit event records.
Technical Specifications
Environmental Conditions
- Installation: Indoor placement with adequate ventilation
- Ambient temperature: -10℃ ~ +50℃
- Relative humidity: Less than 90%, no surface condensation
- Atmospheric pressure: 80 ~ 110 kPa
- Altitude: Below 2000 meters
- Ambient surroundings: Free of conductive dust, corrosive gas and mould that corrode metals or damage insulation components.
Electrical Parameters
| Item | Specifications |
|---|---|
| Operating Power Supply | AC/DC 220V. Special power requirements need to be stated when ordering; Power consumption ≤ 20W |
| Measuring Range | Voltage: 5V ~ 450V, PT loop power consumption: 0.5VA per phase Current: 0.06A ~ 6A, CT loop power consumption: 0.5VA per phase |
| Communication Interface | RS232 / RS485 (optional, to be confirmed upon order); Baud rate: 600 ~ 19200 bps |
| Communication Protocols | Serial Port 1: Exclusive internal communication protocol Serial Port 2: IEC 60870-5-103 Protocol / Modbus Protocol |
Application Scope
This online harmonic monitoring device is applicable to power supply systems ranging from 380V to 220kV. It can be widely deployed in power plants, substations, as well as large-scale industrial and mining facilities including petroleum, coal, steel, metallurgy and chemical plants. It continuously monitors grid harmonic conditions on site, alerts users to harmonic overruns and transmits monitoring data remotely, which effectively safeguards reliable power consumption and standardized power quality management for all types of industrial power systems.